Measuring ranges |
different temperature ranges
in same unit as standard
selectable via jumpers on pcb.
with manual zero point
correction (+/-10K) |
Sensing element |
PT1000, DIN EN 60751, class B |
Deviation
temperature |
+/-0.2K at +25°C |
Connections |
3-wire for 0-10 Vdc
2-wire for 4-20 mA |
Power supply |
24 Vac/dc +/- 10% for output 0-10 Vdc
15-35 Vdc for output 4-20 mA |
Protection type |
IP30 (according to EN 60529) |
Ambient
temperature |
-30°C to +70°C |
Humidity |
< 95% r.H. non-precipitating air |
Protection class |
III (according to EN 60730) |
Standards |
CE conformity,
electromagnetic compatibility
accoring to EN 61326:2006
according to EMC directive 2004/108/EC |
Display |
8-digit display,
cutout 36×14 mm (W x H),
for displaying actual temperature
(only for TRTS 010D and TRTS 420D) |