PART NUMBER & PRICE
Type no. | Output | Display |
TDTH 010 xxx | 0-10 Vdc | No |
TDTH 420 xxx | 4-20 mA | No |
TDTH 010 xxxD | 0-10 Vdc | Yes |
TDTH 420 xxxD | 4-20 mA | Yes |
xxx = probe length in mm; 50, 100, 150, 200, 250 or 300. Examples:
|
KEYWORD TECHNOLOGIES & SERVICES
KEYWORD TECHNOLOGIES & SERVICES
1,990.00฿
Type no. | Output | Display |
TDTH 010 xxx | 0-10 Vdc | No |
TDTH 420 xxx | 4-20 mA | No |
TDTH 010 xxxD | 0-10 Vdc | Yes |
TDTH 420 xxxD | 4-20 mA | Yes |
xxx = probe length in mm; 50, 100, 150, 200, 250 or 300. Examples:
|
Measuring ranges | 8 different temperature ranges in same unit as standard selectable via jumpers on pcb. with manual zero point correction (+/-10K) |
Sensing element | PT1000, DIN EN 60751, class B |
Accuracy | 0.3 K (Kelvin) |
Connections | 3-wire for 0-10 Vdc 2-wire for 4-20 mA |
Power supply | 24 Vac/dc +/- 10% for output 0-10 Vdc 15-35 Vdc for output 4-20 mA |
Ambient temperature |
-30°C to +70°C |
Humidity | < 95% r.H. non-precipitating air |
Protection type | IP65 (according to EN 60529)’ |
Protection class | III (according to EN 60730) |
Housing material |
Plastic, material polyamide, 30% glass-globe-reinforced with quick-locking screws colour pure-white (similar RAL9010) |
Housing dimensions |
72x64x39 mm excluding cable entry gland |
Cable gland | M16, including strail relief |
Standards | CE conformity, electromagnetic compatibility accoring to EN 61326:2006 according to EMC directive 2004/108/EC |
Display | single line display with illumination, cutout 37×15 mm (W x H), for displaying actual temperature (only for TDTH 010D and TDTH 420D) |
Probe material | Stainless steel, 1.4571, V4A |
Probe diameter | 6 mm |
Probe length | 50, 100, 150, 200, 250 or 300 mm |
Mounting | By a plastic mounting flange, included in the delivery of TDTH |