Measuring
range humidity |
to 100% r.H.
(output corresonding to
0-10 Vdc or 4-20 mA) |
Operation
range humidity |
0 to 95% r.H.
(non-pricipitating air) |
Accuracy humidity |
+/-3 % r.H. (20 to 80% ) @ +20°C,
otherwise +/-5% |
Output humidity |
0-10 Vdc or 4-20 mA, see ordering.
working resistance < 800ohm,
see loading resistance diagram |
Measuring
range temp. |
to +50°C (output corresponding to
0-10 Vdc or 4-20 mA or Ohm value) |
Operation
range temp. |
0 to +50°C |
Accuracy temp. |
+/-0.8K @ +20°C,
under standard conditions |
Output temp. |
0-10 Vdc or 4-20 mA or Ohm value |
Ambient
range temp. |
-25 to +50°C (storage)
-5 to +55°C (working) |
Power supply |
24 Vac (+/-20%) or
15-36 Vdc (+/-10%)
for 0-10 Vdc output versions
15-36 Vdc (+/-10%)
for 4-20 mA output versions
(depending on working resistance) |
Power consumtion |
< 1.1 VA / 24Vdc: < 2.2 VA / 24 Vac |
Long-term stability |
+/-1% per year |
Protection class |
III (according to EN 60730) |
Protection type |
IP30 (according to EN 60529) |
Standards |
CE conformity
according to EMC directive 2004/108/EC
accoring to EN 61326-1:2006